Influence of the filling gas mixture on the interruption capability of medium voltage load break switches

Authors

  • T. Krampert Institute for High Voltage Equipment and Grids, Digitalization and Power Economics, RWTH Aachen University, Schinkelstr. 6, 52056 Aachen https://orcid.org/0000-0002-5161-1958
  • M. Bendig Institute for High Voltage Equipment and Grids, Digitalization and Power Economics, RWTH Aachen University, Schinkelstr. 6, 52056 Aachen https://orcid.org/0000-0002-4287-1459
  • A. Moser Institute for High Voltage Equipment and Grids, Digitalization and Power Economics, RWTH Aachen University, Schinkelstr. 6, 52056 Aachen https://orcid.org/0000-0001-6981-510X
  • M. Schaak Siemens AG, Smart Infrastructure Distribution Systems, Carl-Benz-Str. 22, 60386 Frankfurt am Main

DOI:

https://doi.org/10.14311/ppt.2021.2.19

Keywords:

load break switch, alternative gas, thermal interruption capability, dielectric recovery

Abstract

In today’s medium voltage switchgear SF6 is commonly used as insulating and arc quenching medium. Because of its high potential impact on the environment a substitution with an environmentally friendly alternative is pursued. In this paper the influence of the mixing ratio of carbon dioxide nitrogen mixtures as filling gas on the interruption capability in medium voltage load break switches is investigated. The interruption capability is regarded by means of the thermal interruption performance as well as the dielectric recovery of a model load break switch. The model load break switch allows an axial arc blowing with variable pressure and uses an exchangeable nozzle system.

References

M. Seeger, R. Smeets, J. Yan, et al. Recent development of alternative gases to SF6 for switching applications. Electra, 291, 2017.

United Nations. Kyoto protocol to the united nations framework convention on climate change, 1998.

T. Uchii, Y. Hoshina, H. Kawano, et al. Fundamental research on SF6-free gas insulated switchgear adopting CO2 gas and its mixtures. In International Symposium on EcoTopia Science, pages 516–520, 2007.

M. Bendig, N. Götte, T. Krampert, et al. A method to determine the rate of the dielectric recovery in a medium voltage load break switch with a free burning switching arc. In 22nd International Conference on Gas Discharges and Their Applications, 2018.

M. Bendig, T. Krampert, N. Götte, et al. Investigations on the effect of the nozzle material on the interruption capability of a medium voltage load break switch. Plasma Physics and Technology, 6(1):15–18, 2019. doi:10.14311/ppt.2019.1.15.

P. G. Nikolic, A. Kurz, M. Hoffacker, and A. Schnettler. Investigations on the dielectric strength of carbon dioxide and carbon dioxide mixtures for the application in gas insulated switchgear. In IEEE International Power Modulator and High Voltage Conference, 2012.

P. Sturm, M. Leuenberger, C. Sirignano, et al. Permeation of atmospheric gases through polymer o-rings used in flasks for air sampling. Journal of Geophysical Research: Atmospheres, 109(D4), 2004. doi:10.1029/2003JD004073.

M. Bendig and M. Schaak. Design rules for environmentally friendly medium voltage load break switches. IEEE Transactions on Power Delivery, 2020. doi:10.1109/TPWRD.2020.3024983.

CIGRE. Dry air, N2, CO2 and N2-SF6 mixtures for gas-insulated systems: Technical brochure 730.

K. Niayesh and M. Runde. Power Switching Components: Theory, Applications and Future Trends. Power Systems. Springer International Publishing, 2017. ISBN 9783319514598. doi:10.1007/978-3-319-51460-4.

E. Jonsson, N. S. Aanensen, and M. Runde. Current interruption in air for a medium-voltage load break switch. IEEE Transactions on Power Delivery, 29(2):870–875, 2014. doi:10.1109/TPWRD.2013.2280300.

N. Götte, M. Bendig, T. Krampert, et al. Experimental and simulative study on the influence of the electrical field distribution on the dielectric switching behavior of natural gases. In 22nd International Conference on Gas Discharges and Their Applications, 2018.