Connection Temperatures during the Mokrsko Fire Test

Authors

  • J. Chlouba
  • F. Wald

DOI:

https://doi.org/10.14311/1101

Keywords:

Fire test, FE simulation, fire safe connection, temperature prediction, Angelina beam, compartment fire

Abstract

The Mokrsko fire test focused on the overall behaviour of the structure, which cannot be observed on the separate elements, and also on the temperature of connections with improved fire resistance. During the test, measurements were made of the temperature of the gas and of the elements, the overall and relative deformations, gas pressure, humidity, the radiation of the compartment to structural element and the external steel column, transport of the moisture through the walls, and also the climatic conditions. The results of the test show the differences between the behaviour of the element and the behaviour of the structure exposed to high temperatures during a fire. The collapse of the composite slab was reached. The results of the numerical simulations using the SAFIR program compared well with the measured temperature values in the structure and also in the connections. 