The Effect of Fault States of the Twelve-pulse Rectifier During the Recuperation

Authors

  • Ladislav Mlynařík University of Pardubice, Pardubice
  • Radovan Doleček University of Pardubice, Pardubice

Abstract

The paper deals with analysis of states from the
viewpoint of the rectifier DC side . In the case of diode
breakdown the interphase short-circuit occurs and the
transformer is disconnected from the primary side by a
high-speed switch. After disconnecting the DC current of a
recuperative traction vehicle influences the circuit. The
fault states of the twelve-pulse rectifier in a substation of 3
kV DC traction system used at railways in the Czech
Republic are analyzed. The situation at the rectifier diode
breakdown and at the same time recuperative vehicles in
power supply section is examined. The vehicle with
recuperation can increase strain of elements in power
supply system under certain conditions during fault states of
the rectifier. The simulation computer model was created
for analysis of current waveforms in trolley line at this
situation. All simulations were created by the program
PSpice. The main goal is to analyze the endanger of power
supply system elements and to present the recommendation
for increasing the reliability of this mentioned power supply
system.

Author Biographies

Ladislav Mlynařík, University of Pardubice, Pardubice

The Jan Perner Transport Faculty, Department of electrical and electronic engineering and signalling in transport (KEEZ)

Radovan Doleček, University of Pardubice, Pardubice

The Jan Perner Transport Faculty, Department of electrical and electronic engineering and signalling in transport (KEEZ)

References

K. Hlava: Elektromagnetická kompatibilita (EMC) drážních

zařízení. University of Pardubice, Pardubice, 2004, ISBN 80-

-637-0.

F. R. Holmstrom, D. Turner, E. Fernald, “Rail transit EMIEMC“,

in: Electromagnetic Compatibility Magazine, Vol.1,

Issue1, pp.79-82, 2012, ISSN 2162-2264.

M. V. Petkova, “Integration for EMC and network rail's

management proces“, in: Railway Electrification Infrastructure

and Systems, pp. 232-239, London, 2011, ISBN 978-1-84919-

-6.

D. Gonzalez, F. Manzanedo, “Optimal design of a D.C. railway

power supply system“, in: Electric Power Conference, 2008,

pp.1–6, 2009, Vancouver, BC, ISBN 978-1-4244-2895-3.

R. Langella, A. Sollazzo, A. Testa, “Modeling waveform

distortion produced by DC locomotive conversion system“. Part

: Locomotive model, in: Harmonics and Quality of Power, 2004,

pp. 477-482, ISBN 0-7803-8746-5.

“Calculating of peak value and steady-state value of short-circuit

current at external short-circuit on bridge rectifier with silicon

diodes“, Report, ABB, Poland, 2006.

J. Pavelka, Z. Čeřovský, J. Lettl: Výkonová elektronika. ČVUT,

Prague, 2007, ISBN 978-80-01-03626-6.

J. Ibl: Průmyslová elektronika II.část: Rtuťové usměrňovače.

SNTL, Prague, 1955.

Calculating of peak value and steady-state value of short-circuit

current at external short-circuit on bridge rectifier with silicon

diodes. ABB Poland, 2006.

C. C. Herskind, H. L. Kellogg: Rectifier fault

currents. Transactions AIEE, pp. 145-150, 1945.

C. C. Herskind, H. L. Kellogg, A. Schmidt: Rectifier fault

currents-II. Transactions AIEE, pp. 243-252, 1949.

K. Hlava: Parametry odběru elektrické energie dvanáctipulzním

trakčním usměrňovačem v závislosti na jeho zatížení. The

Scientific and Technological Anthology of Czech railways n. 14,

Prague, General office of Czech railways, 2002. [Online]

<http://www.cdrail.cz/VTS/vts14.html>. [Accessed: 03 Jan.

ISSN 1214-9047.

Downloads

Published

2020-03-30

Issue

Section

Articles