PERFORMANCE-BASED FIRE DESIGN OF STEEL STRUCTURES OF HELSINKI OLYMPIC STADIUM

Authors

  • Mikko Salminen
  • Jukka Hietaniemi

DOI:

https://doi.org/10.14311/asfe.2015.016

Abstract

This paper presents an overview of the fire safety analysis conducted for the steel trusses of Helsinki Olympic Stadium stand. The analysis were conducted using advanced calculation models (FDS and SAFIR). It is shown that the predefined design solution (R60 fire protection with sprinklers) can be replaced by fire protection to class R15 (no sprinkler system) without sacrificing safety when some other passive protection means are applied. The good design solution in this case required highly iterative design process and smooth co-operation between client, architects, structural engineers and fire safety consultants.

Downloads

Published

2016-01-18