MODEL OF HEAT SIMULATOR FOR DATA CENTERS

Authors

  • Jan Novotný ČVUT v Praze FS
  • Jiří Nožička ČVUT v Praze FS

DOI:

https://doi.org/10.14311/AP.2016.56.0301

Keywords:

data center, cooling, heat simulator, PIV, measurement,

Abstract

The aim of this paper is to present a design and a development of a heat simulator, which will be used for a flow research in data centers. The designed heat simulator is based on an ideological basis of four-processor 1U Supermicro server. The designed heat simulator enables to control the flow and heat output within the range of 10–100 %. The paper covers also the results of testing measurements of mass flow rates and heat flow rates in the simulator. The flow field at the outlet of the server was measured by the stereo PIV method. The heat flow rate was determined, based on measuring the temperature field at the inlet and outlet of the simulator and known mass flow rate.