Response Analysis of an RC Cooling Tower Under Seismic and Windstorm Effects
DOI:
https://doi.org/10.14311/890Keywords:
cooling tower, wind load, earthquake, ductility, dynamic responseAbstract
The paper compares the RC structure of a cooling tower unit under seismic loads and under strong wind loads. The calculated values of the envelopes of the displacements and the internal forces due to seismic loading states are compared with the envelopes of the loading states due to the dead, operational and live loads, wind and temperature actions. The seismic effect takes into account the seismic area of ground motion 0.3 g and the ductility properties of a relatively rigid structure. The ductility is assessed as the reduction in seismic load. In this case the actions of wind pressure are higher than the seismicity effect under ductility correction. The seismic effects, taking into account the ductility properties of the structure, are lower than the actions of the wind pressure. The other static loads, especially temperature action due to the environment and surface insulation are very important for the design of the structure.Downloads
Download data is not yet available.
Downloads
Published
2006-01-06
Issue
Section
Articles
How to Cite
Makovička, D. (2006). Response Analysis of an RC Cooling Tower Under Seismic and Windstorm Effects. Acta Polytechnica, 46(6). https://doi.org/10.14311/890